Examining the impact of filling ratio on thermosyphon performance in passive energy recovery processes with dual effects of evaporative cooling: An experimental study

被引:0
|
作者
ALsayah, Ahmed Mohsin [1 ,2 ]
Faraj, Johain J. [1 ]
Eidan, Adel A. [3 ]
Alshukri, Mohammed J. [2 ,4 ]
机构
[1] Middle Tech Univ, Engn Tech Coll, Baghdad, Iraq
[2] Islamic Univ, Tech Engn Coll, Refrigerat & Air Condit Dept, Najaf, Iraq
[3] Al Furat Al Awsat Tech Univ ATU, Engn Tech Coll Al Najaf, Najaf, Iraq
[4] Kufa Univ, Fac Engn, Dept Mech Engn, Najaf, Iraq
关键词
energy efficiency; evaporative cooling; HVAC application; passive energy Saving; thermosyphon HPHE;
D O I
10.1002/htj.23147
中图分类号
O414.1 [热力学];
学科分类号
摘要
The thermosyphon heat exchanger contributes significantly to the improvement of energy conservation technology and has been used in multiple applications, raising the possibility of further studies to contribute to increasing the efficiency of heat pipes. This experimental study examines the different filling ratios of pure Acetone liquid inside a WHPHE integrated with the double-effect of evaporative cooling to improve the energy-saving technology. This work studies changing the filling ratio of pure acetone working fluid to investigate the effect of the filling ratio on heat exchanger performance in waste energy recovery technology. The heat exchanger was used with four rows and five tubes per row arranged in a staggered manner. The filling ratio of acetone inside the heat pipe was changed from 50% to 100%. The effect of the mass flow rate of air flowing in direct evaporative cooling on energy conservation technology was studied while the mass flow rate of air through indirect cooling remains constant in addition to the effect of ambient temperature. The results showed that the best filling percentage was between 80% at different temperatures, and the highest energy recovery percentage was when it was at the filling percentage of 80% in the presence of evaporative cooling.
引用
收藏
页码:4572 / 4587
页数:16
相关论文
共 9 条
  • [1] Experimental study on cooling performance of air conditioning system with dual independent evaporative condenser
    Liu, Huanwei
    Zhou, Qiushu
    Liu, Yuling
    Wang, Peifeng
    Wang, Defa
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2015, 55 : 85 - 92
  • [2] Experimental study of cooling effects of a passive evaporative cooling wall constructed of porous ceramics with high water soaking-up ability
    He, Jiang
    Hoyano, Akira
    BUILDING AND ENVIRONMENT, 2010, 45 (02) : 461 - 472
  • [3] An experimental and numerical study on the thermal performance of a loop thermosyphon integrated with latent thermal energy storage for emergency cooling in a data center
    Ma, Xiaowei
    Zhang, Quan
    Zou, Sikai
    ENERGY, 2022, 253
  • [4] Experimental study on cooling performance and energy saving of gas engine-driven heat pump system with evaporative condenser
    Liu, Huanwei
    Zhou, Qiushu
    Zhao, Haibo
    ENERGY CONVERSION AND MANAGEMENT, 2016, 123 : 200 - 208
  • [5] Experimental study on energy performance of a split air-conditioner by using variable thickness evaporative cooling pads coupled to the condenser
    Martinez, P.
    Ruiz, J.
    Cutillas, C. G.
    Martinez, P. J.
    Kaiser, A. S.
    Lucas, M.
    APPLIED THERMAL ENGINEERING, 2016, 105 : 1041 - 1050
  • [6] A Simulation and Experimental Study of the Impact of Passive and Active Facade Systems on the Energy performance of Building Perimeter Zones
    Chan, Ying-Chieh
    Tzempelikos, Athanasios
    ASHRAE TRANSACTIONS 2012, VOL 118, PT 2, 2012, 118 : 149 - 156
  • [7] Performance improvement of a pump running as turbine for energy recovery considering the effects of polymer additives: An experimental study
    Bayatloo, Mohammad
    Koohizadhikoei, Reza
    Ghorani, Mohammad Mahdi
    Riasi, Alireza
    Hamzehnava, Ghodratollah
    SUSTAINABLE ENERGY TECHNOLOGIES AND ASSESSMENTS, 2023, 57
  • [8] The synthetical effects of passive radiative cooling building envelopes and surrounding buildings on building daylighting and energy performance: A case study in Miami
    Su, Xiaosong
    Luo, Yongqiang
    Zhang, Ling
    SUSTAINABLE CITIES AND SOCIETY, 2025, 121
  • [9] Experimental investigation of the effects of energy ratio and combustion chamber design on engine performance and emissions in a hydrogen-diesel dual-fuel CRDI engine
    Gultekin, Nurullah
    Ciniviz, Murat
    ATMOSPHERIC POLLUTION RESEARCH, 2024, 15 (09)