Coupled building simulation and CFD for real-time window and HVAC control in sports space

被引:3
|
作者
Li, Yu [1 ,2 ]
Li, Lingling [1 ,2 ]
Cui, Xue [3 ]
Shen, Pengyuan [4 ,5 ]
机构
[1] Harbin Inst Technol, Sch Architecture & Design, Harbin 150001, Peoples R China
[2] Minist Ind & Informat Technol, Key Lab Cold Reg Urban & Rural Human Settlement En, Harbin 150001, Peoples R China
[3] Hong Kong Polytech Univ, Fac Construct & Environm, Dept Bldg & Real Estate, Hong Kong, Peoples R China
[4] Tsinghua Univ, Shenzhen Int Grad Sch, Shenzhen 518055, Peoples R China
[5] Harbin Inst Technol, Shenzhen 518055, Peoples R China
来源
基金
中国国家自然科学基金;
关键词
Building energy simulation; CFD; Co-simulation; Sports buildings; Real-time control; INDOOR THERMAL ENVIRONMENT; NATURAL VENTILATION; ENERGY SIMULATION; FLUID-DYNAMICS; AIR-FLOW; COMFORT; OPTIMIZATION;
D O I
10.1016/j.jobe.2024.110731
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Accurately predicting players' thermal comfort in large sports spaces for real-time window and HVAC operations presents significant challenges due to non-uniform thermal distributions. Standalone building energy simulation (BES) typically assumes the entire targeted space as a uniform thermal zone, which fails to capture these variances. Conversely, Computational Fluid Dynamics (CFD) simulation can predict indoor thermal environments with precision but often struggles with determining accurate boundary conditions. This study introduces a coupled BES and CFD simulation method tailored for real-time window and HVAC control in sports spaces. A case study was conducted in a prototypical national fitness hall to evaluate the effectiveness of the proposed method. The thermal comfort and cooling energy results from the co-simulation-based control were compared with those from standalone EnergyPlus simulation-based control and fixed-schedule window and HVAC operations, which served as baselines. The results indicate that the proposed method enhanced thermal comfort by 68.5 % compared to constantly-scheduled window operations and achieved daily energy savings of up to 43.5 % versus constantly- scheduled HVAC operations. Furthermore, significant discrepancies in Average Predicted Mean Vote (PMV) PMV ) or Average Adaptive Predicted Mean Vote ( aPMV ) as well as daily cooling energy consumption between the BES-CFD co-simulation and standalone EnergyPlus simulation were identified, ranging from-0.53 to 1.83 for PMV ( aPMV ) and-2444.6 to 1266.5 kWh for cooling energy. This study contributes novel methods for real-time window and HVAC control in sports buildings towards thermally comfortable and energy-efficient sports environments.
引用
收藏
页数:22
相关论文
共 50 条
  • [1] Energy efficient building HVAC control algorithm with real-time occupancy prediction
    Shi, Jie
    Yu, Nanpeng
    Yao, Weixin
    8TH INTERNATIONAL CONFERENCE ON SUSTAINABILITY IN ENERGY AND BUILDINGS, SEB-16, 2017, 111 : 277 - 286
  • [2] Real-time model predictive cooling control for an HVAC system in a factory building
    Ra, Seon Jung
    Kim, Jin-Hong
    Park, Cheol Soo
    ENERGY AND BUILDINGS, 2023, 285
  • [3] Quantum computing for future real-time building HVAC controls
    Deng, Zhipeng
    Wang, Xuezheng
    Dong, Bing
    APPLIED ENERGY, 2023, 334
  • [4] A real-time simulation tool for real-time control
    Kwon, WH
    Kim, KB
    Moon, SY
    Choi, SG
    Kim, YS
    ALGORITHMS AND ARCHITECTURES FOR REAL-TIME CONTROL 1997, 1997, : 325 - 329
  • [5] Building a model for real-time simulation
    Lee, K
    Fishwick, PA
    FUTURE GENERATION COMPUTER SYSTEMS-THE INTERNATIONAL JOURNAL OF ESCIENCE, 2001, 17 (05): : 585 - 600
  • [6] Optimal Real-Time Energy Management in Apartment Building Integrating Microgrid With Multizone HVAC Control
    Rezaei, Ehsan
    Dagdougui, Hanane
    IEEE TRANSACTIONS ON INDUSTRIAL INFORMATICS, 2020, 16 (11) : 6848 - 6856
  • [8] Real-time simulation of control system for tall building with podium structure
    Chen, Jing
    Ren, Chaozhi
    DCABES 2006 PROCEEDINGS, VOLS 1 AND 2, 2006, : 1345 - 1347
  • [10] REAL-TIME SIMULATION FOR SPACE STATION
    STJOHN, RH
    MOORMAN, GJ
    BROWN, BW
    PROCEEDINGS OF THE IEEE, 1987, 75 (03) : 383 - 398