摘要
Oil-immersed transformers are widely used in power systems. When an arc fault occurs inside a transformer, the surrounding oil is rapidly pyrolyzed. These high-temperature, flammable gases are compressed into a high-pressure bubble, which is likely to cause tank deformations, explosions, and fires. Currently, related simulations on tank internal pressure and transformer fires are based on a constant gas composition, a constant gas production rate of 0.1 L/kJ, and a constant bubble temperature of 2000 K. This paper deals with a case of a power-frequency arc (5 kA, 30 mm, 80 ms) in transformer oil. The time-varying characteristics of pyrolyzed gas production, composition, and temperature are experimentally investigated. The percentage of hydrogen changes considerably, decreasing from 85.2 % to 70%. The overall gas production rate increases slowly from 0.0574 L/kJ in the first 2.5 ms to 0.0982 L/kJ in 80 ms. The local temperature inside the main bubble (30 mm from the arc) decreases gradually from 2200 K to 1400 K, while the average bubble temperature decreases from 2550 K to 550 K. This case and these results provide an experimental basis for the parameter selections in the simulations about transformer internal pressure and fire progression.
引用
收藏
页数:12
相关论文
共 50 条
  • [1] Optical Signal Characteristics of Power Frequency Arc in Transformer Oil
    Jia, Shuangrui
    Jia, Yunfei
    Luo, Xun
    Ji, Shengchang
    Lv, Liang
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2024, 39 (01) : 675 - 678
  • [2] Overview on the Characteristics of Power Frequency Arc in Transformer Oil and Transformer Explosion Protection
    Jia Y.
    Ji S.
    Li J.
    Jia S.
    Luo X.
    Wang K.
    Sun J.
    [J]. Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2024, 44 (07): : 2910 - 2926
  • [3] Characteristics of gas and residues produced from electric arc pyrolysis of waste lubricating oil
    Song, Geum-Ju
    Seo, Yong-Chil
    Pudasainee, Deepak
    Kim, In-Tae
    [J]. WASTE MANAGEMENT, 2010, 30 (07) : 1230 - 1237
  • [4] Simulation of Vacuum Arc Characteristics at Different Moments Under Power-Frequency Current
    王立军
    杨鼎革
    贾申利
    王流火
    史宗谦
    [J]. Plasma Science and Technology, 2012, (03) : 227 - 234
  • [5] Simulation of Vacuum Arc Characteristics at Different Moments Under Power-Frequency Current
    Wang Lijun
    Yang Dingge
    Jia Shenli
    Wang Liuhuo
    Shi Zongqian
    [J]. PLASMA SCIENCE & TECHNOLOGY, 2012, 14 (03) : 227 - 234
  • [6] Simulation of Vacuum Arc Characteristics at Different Moments Under Power-Frequency Current
    王立军
    杨鼎革
    贾申利
    王流火
    史宗谦
    [J]. Plasma Science and Technology, 2012, 14 (03) : 227 - 234
  • [7] A power-frequency measuring-transformer current-voltage converter
    Malinovskii, V. N.
    Malinovskaya, V. V.
    [J]. MEASUREMENT TECHNIQUES, 2006, 49 (05) : 495 - 499
  • [8] A power-frequency measuring-transformer current-voltage converter
    V. N. Malinovskii
    V. V. Malinovskaya
    [J]. Measurement Techniques, 2006, 49 : 495 - 499
  • [9] Power-frequency magnetic field calculation around an indoor transformer substation
    Geri, A
    Veca, GM
    [J]. BOUNDARY ELEMENTS XXVII: INCORPORATING ELECTRICAL ENGINEERING AND ELECTROMAGNETICS, 2005, 39 : 695 - 704