Thermal Environment Analysis and Optimization for Large Space Buildings with Radiant Cooling Floors: A Case Study of Xianyang International Airport

被引:1
|
作者
Hu, Rong [1 ]
Wang, Haolin [1 ]
Liang, Junqi [1 ]
Li, Xiaoping [2 ]
Zheng, Wenheng [1 ]
Liu, Gang [3 ]
机构
[1] Guilin Univ Elect Technol, Sch Architecture & Traff Engn, Guilin 541004, Peoples R China
[2] China Acad Bldg Res, Beijing 100013, Peoples R China
[3] Cent South Univ, Sch Energy Sci & Engn, Changsha 410083, Peoples R China
关键词
airport terminal; radiant cooling floor; control strategy; PMV-PPD; CFD; COMFORT CONDITIONS; INDOOR; SYSTEM; AIR; PERFORMANCE; QUALITY;
D O I
10.3390/buildings14051355
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Radiant cooling floors combined with ventilation systems have been widely applied in large space buildings. However, there has been a lack of research on system control strategies for their adaptation to weather changes. This study aimed to find control strategies for radiant cooling floors combined with displacement ventilation systems used in large space buildings in order to achieve energy conservation and environmental improvement. Supply air temperature and cooling surface temperature were determined to be the control variables. It was found that cooling capacity of the combined system and the comfort index, PMV (predicted mean vote), were linear in relation to the supply air temperature and cooling surface temperature. The linear equations regarding cooling capacity and PMV were established separately using environment data, and then the optimal region was determined. A case study on Terminal 3 of Xi'an Xianyang International Airport was conducted. The thermal environment was investigated through on-site measurements, questionnaires, and numerical simulations with CFD (computational fluid dynamics). It was found that supply air temperature and cooling surface temperature had a significant impact on PMV, and less impact on the cooling capacity. Therefore, it was determined that the supply air temperature should be altered first when the indoor temperature exceeds the upper limit, and then the cooling surface temperature should be changed if the indoor environment continues to overheat with the supply air temperature set to 18 degrees C. Thus, the supply air temperature was kept at 18 degrees C, and the floor surface temperature was set to be 22 degrees C on a high-temperature day. The average PMV was 0.87, and the cooling capacity of the combined system was 200 W/(m2<middle dot>K), according to the CFD simulation. In addition, the surface heat transfer coefficient of the cooling floor was found to be 10.26 W/(m2<middle dot>K). This research provides important references for the design and operational management of radiant cooling floors in large space buildings.
引用
收藏
页数:26
相关论文
共 9 条
  • [1] A comprehensive optimization study of personal cooling radiant desks integrated to HVAC system for energy efficiency and thermal comfort in office buildings
    Ismail, Nagham
    Ouahrani, Djamel
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION, 2023, 156 : 54 - 71
  • [2] Case Study of Space Optimization Simulation of Existing Office Buildings Based on Thermal Buffer Effect
    Gan, Shenqi
    Chen, Wenxiang
    Feng, Jiawang
    [J]. BUILDINGS, 2024, 14 (06)
  • [3] Evaluation of Thermal Comfort and Energy Consumption of Water Flow Glazing as a Radiant Heating and Cooling System: A Case Study of an Office Space
    Moreno Santamaria, Belen
    Ama Gonzalo, Fernando del
    Aguirregabiria, Benito Lauret
    Hernandez Ramos, Juan A.
    [J]. SUSTAINABILITY, 2020, 12 (18)
  • [4] Analysis of a Thermal Energy Storage Tank in a Large District Cooling System: A Case Study
    Abd Majid, Mohd Amin
    Muhammad, Masdi
    Hampo, Chima Cyril
    Akmar, Ainul Bt
    [J]. PROCESSES, 2020, 8 (09)
  • [5] Light Environment Analysis and Design Strategies of Large Commercial Buildings-A Case Study in Harbin
    Hong Jin
    Xin-Xin Li
    [J]. Journal of Harbin Institute of Technology(New series), 2014, (04) : 1 - 9
  • [6] Light Environment Analysis and Design Strategies of Large Commercial Buildings-A Case Study in Harbin
    Hong Jin
    Xin-Xin Li
    [J]. Journal of Harbin Institute of Technology., 2014, 21 (04) - 9
  • [7] Cost-benefit analysis of micro WtE incinerator applications in an urban environment: A case study at the Hong Kong International Airport
    Zu, Fuhao
    Zhang, Xueqing
    [J]. WASTE MANAGEMENT, 2023, 159 : 134 - 145
  • [8] An economic evaluation of refrigeration and air-conditioning system retrofit in large-scale public buildings: A case study of Beijing Capital International Airport Terminals
    Liu, Yuming
    Liu, Tingting
    Ji, Boya
    Wang, Binyu
    [J]. JOURNAL OF CLEANER PRODUCTION, 2020, 245
  • [9] Numerical Simulation of the Thermal Environment during Summer in Coastal Open Space and Research on Evaluating the Cooling Effect: A Case Study of May Fourth Square, Qingdao
    Zhang, Ying
    Hu, Xijun
    Cao, Xilun
    Liu, Zheng
    [J]. SUSTAINABILITY, 2022, 14 (22)