Active Fault-Locating Scheme for Hybrid Distribution Line Based on Mutation of Aerial-Mode Injected Pulse

被引:0
|
作者
Jiang, Zhuang [1 ]
Zeng, Xiangjun [1 ]
Liu, Feng [1 ]
Yu, Kun [1 ]
Bi, Lanxi [1 ]
Wang, Youpeng [1 ]
机构
[1] Changsha Univ Sci & Technol, State Key Lab Disaster Prevent & Reduct Power Grid, Changsha 410114, Peoples R China
基金
中国国家自然科学基金;
关键词
hybrid distribution line; pulse injection; aerial-mode traveling wave; zero-mode traveling wave; active fault location; TRANSMISSION-LINE; ALGORITHM; TRANSFORM;
D O I
10.3390/en17102248
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Due to the overlap of initial traveling wave signals, the traveling wave propagation process in hybrid distribution lines is complicated to analyze. The most significant challenge posed by the traditional passive traveling wave-locating method for hybrid distribution lines lies in identifying the fault section and distinguishing the reflected wave from the fault point or the hybrid connection points. Based on this approach, with the application of the aerial-mode component of the pulse signal generated at the fault point, a fault-section-identification and fault-locating scheme for hybrid distribution feeders with active pulse injection is proposed. When power in a line is cut after a single-to-line ground (SLG) fault occurs, the same pulse is injected into the three phases from the neutral point of the coupling capacitor bank to construct the zero-mode component, which propagates to the SLG fault three-phase asymmetrical point, producing an aerial-mode component that is reflected back to the first end of the line. With the application of the arrival time of an aerial-mode wavefront, it is simple to locate the SLG fault for arbitrary forms of hybrid lines. The simulation results confirm the feasibility of the fault-locating scheme under different feeders, different fault locations, and fault resistances. The results of the experiments confirm the high practical value of the proposed method.
引用
收藏
页数:21
相关论文
共 7 条
  • [1] A Non-Unit Line Protection Scheme for MMC-MTDC Grids Based on Aerial-Mode Voltage Traveling Waves
    Zhang, Shuo
    Zou, Guibin
    Xu, Chunhua
    Sun, Chenjun
    2018 INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY (POWERCON), 2018, : 2482 - 2489
  • [2] Pilot Protection Scheme for HVDC Transmission Line Based on Fault Component of Aerial Mode Current
    Dai W.
    Lin S.
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2020, 44 (19): : 142 - 149
  • [3] A Hybrid Protection Scheme for Active Distribution Networks Based on Fault Components Principle
    Zhao, Rui-feng
    Su, Biao-long
    Yu, Zhi-wen
    Wang, Kai-lin
    Lu, Jian-gang
    JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY, 2024, : 141 - 155
  • [4] Fault Line Diagnosis Scheme of Active Distribution System Based on Time-Sequence Convolution Residual Network
    Chu X.
    Bao Z.
    Xu L.
    Yan Y.
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2023, 38 (08): : 2178 - 2190
  • [5] Single-phase ground fault line selection method in active distribution networks based on high-voltage inverter injected signals
    Liu, Zhengyi
    Deng, Changhong
    DYNA, 2019, 94 (05): : 539 - 545
  • [6] A Single-Phase Ground Fault Line Selection Method in Active Distribution Networks Based on Transformer Grounding Mode Modification
    Su, Shi
    Xie, Qingyang
    Ma, Pengfei
    Li, Yuan
    Chen, Fahui
    Zhang, Jing
    Li, Botong
    Wang, Changqi
    ENERGIES, 2024, 17 (18)
  • [7] Fault-Line Selection Method in Active Distribution Networks Based on Improved Multivariate Variational Mode Decomposition and Lightweight YOLOv10 Network
    Hou, Sizu
    Wang, Wenyao
    Energies, 2024, 17 (19)