Facade flame depth coming out from the fire compartment opening subject the external sideward wind

被引:0
|
作者
Sun, Xiepeng [1 ,2 ,3 ]
Yi, Jiwei [1 ]
Han, Yu [1 ]
Zhang, Xiaolei [1 ]
Tang, Fei [1 ]
Hu, Longhua [1 ]
机构
[1] Univ Sci & Technol China, State Key Lab Fire Sci, Hefei 230026, Anhui, Peoples R China
[2] State Key Lab Bldg Safety & Built Environm, Beijing, Peoples R China
[3] Natl Engn Res Ctr Bldg Technol, Beijing, Peoples R China
基金
中国国家自然科学基金;
关键词
Fuel combustion; Facade flame; Energy release; External sideward wind; Flame depth; HEAT-TRANSFER; TEMPERATURE PROFILE; POOL FIRES; AIR-FLOW; PRESSURE; BEHAVIOR; EVOLUTION; GEOMETRY; HEIGHTS; PLUME;
D O I
10.1016/j.energy.2024.132093
中图分类号
O414.1 [热力学];
学科分类号
摘要
When a fuel leakage/energy release (i.e., combustion, fire) inside a compartment, the external facade flame characteristics through opening are of great significance for protecting human life and property, as well as assessment of its risk and impact to urban environment. This work investigates facade flame depth coming out from fire compartment opening with fuel combustion/energy release inside the compartment for underventilated condition under sideward wind, which is a fundamental parameter in describing facade morphological characteristics in particular building fire, meanwhile still no work can be found in previous studies. Results show that, as sideward wind speed increases, the flame depth first increases a bit then decreases significantly. A CFD simulation is carried out to understand flow field controlling facade flame depth under windless and sideward wind situations. A physical analysis is presented on account of mechanisms of complex interaction among sideward wind inertial, outflow momentum through opening, and flame buoyancy flux are proposed based on controlling mechanisms, which well represents the facade flame depth by a non-dimensional function under sideward wind condition. This study makes an important new contribution comparing with previous knowledge, and has potential practical value for fuel combustion inside confined space and the corresponding numerical model verification.
引用
收藏
页数:15
相关论文
共 29 条
  • [1] Facade flame height and horizontal extending distance from opening of compartment fire with external sideward wind
    Hu, Longhua
    Sun, Xiepeng
    Zhang, Xiaolei
    Ren, Fei
    PROCEEDINGS OF THE COMBUSTION INSTITUTE, 2019, 37 (03) : 3859 - 3867
  • [2] Temperature evolution and transition inside fire compartment with an opening subject to external sideward wind
    Sun, Xiepeng
    Zhang, Xiaolei
    Hu, Longhua
    Kuwana, Kazunori
    PROCEEDINGS OF THE COMBUSTION INSTITUTE, 2019, 37 (03) : 3869 - 3877
  • [3] Facade flame height ejected from an opening of fire compartment under external wind
    Hu, Longhua
    Hu, Kaizhi
    Ren, Fei
    Sun, Xiepeng
    FIRE SAFETY JOURNAL, 2017, 92 : 151 - 158
  • [4] Experimental study on flame pulsation behavior of external venting facade fire ejected from opening of a compartment
    Sun, Xiepeng
    Hu, Longhua
    Zhang, Xiaolei
    Ren, Fei
    Yang, Yong
    Fang, Xiang
    PROCEEDINGS OF THE COMBUSTION INSTITUTE, 2021, 38 (03) : 4485 - 4493
  • [5] Flame behavior from an opening at different elevations on the facade wall of a fire compartment
    Lu, Kaihua
    Wang, Zichang
    Ding, Yanming
    Wang, Jie
    Zhang, Jianping
    Delichatsios, Michael A.
    Hu, Longhua
    PROCEEDINGS OF THE COMBUSTION INSTITUTE, 2021, 38 (03) : 4551 - 4559
  • [6] An experimental study on vertical temperature profile of facade fire plume ejected from compartment with an opening subjected to external wind normal to facade
    Ren, Fei
    Hu, Longhua
    Sun, Xiepeng
    Hu, Kaizhi
    INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2018, 130 : 94 - 99
  • [7] Experimental study on flame radiation fraction of facade fire ejected from opening of a compartment
    Ren, Fei
    Hu, Longhua
    Sun, Xiepeng
    Hu, Kaizhi
    APPLIED THERMAL ENGINEERING, 2018, 129 : 573 - 576
  • [8] Study on the fire characteristics of the compartment with two opposing openings under external sideward wind
    He, Mingming
    Hu, Haowei
    Ji, Jie
    Chen, Shuo
    Meng, Xiangmin
    Gao, Zihe
    Li, Man
    FIRE SAFETY JOURNAL, 2022, 130
  • [9] Facade flame height ejected from opening of a compartment under the coupling effect of side walls and ambient wind
    Fang, Xiang
    Ren, Fei
    Zhang, Xiaolei
    Sun, Xiepeng
    Yang, Yong
    Hu, Longhua
    FIRE SAFETY JOURNAL, 2020, 112
  • [10] Evolutions of gas temperature inside fire compartment and external facade flame height with a casement window
    Sun, Xiepeng
    Hu, Longhua
    Yang, Yong
    Ren, Fei
    Fang, Xiang
    JOURNAL OF HAZARDOUS MATERIALS, 2020, 381