Incipient interturn fault detection for ONAN power transformers using electrothermal characteristic fusion analysis

被引:0
|
作者
Zhang, Lijing [1 ]
Sheng, Gehao [1 ]
Zhou, Nan [2 ]
Ni, Zizhan [1 ]
Jiang, Xiuchen [1 ]
机构
[1] Shanghai Jiao Tong Univ, Dept Elect Engn, Shanghai 200240, Peoples R China
[2] Nanyang Technol Univ, Sch Elect & Elect Engn, Singapore, Singapore
关键词
fault diagnosis; power transformers; thermal analysis; DISSOLVED-GAS ANALYSIS; WINDING FAULT; MODEL; OIL;
D O I
10.1049/gtd2.13166
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Existing interturn fault detecting methods rely on winding impedance, winding current, and dissolved gases. They are effective only when the insulation is severely damaged. This paper proposes a novel detection method based on fusion analysis of electrothermal characteristics including winding currents, temperatures of four areas on the tank wall, top oil and ambient temperatures, which can identify the interturn fault at an early stage. When an incipient interturn fault occurs, the heat generated by the faulty turns is transferred to the oil and tank wall, leading to an increase in top oil and tank wall temperatures. Thus, the incipient fault can be detected by analysing these electrothermal characteristic parameters. Borrowing the idea of digital twin (DT), this method establishes a high-fidelity simulation model to simulate the transformer electrothermal characteristics under different operating conditions. Afterward, an intelligent neural network is adopted to extract the quantitative relationship between the eight feature attributions and fault conditions. Finally, this neural network is utilized to detect the incipient interturn fault for the transformer entity. Case studies are conducted on a 100 kVA transformer with oil natural air natural (ONAN) cooling mode. The detection accuracy is improved by 68.5% compared to the winding current-based method. The manuscript proposes a novel method based on fusion analysis of electrothermal characteristics for detecting incipient interturn fault of ONAN transformers. This method relies on winding currents, ambient temperature, top oil temperature, and the temperatures in four areas of the tank wall, which can identify the early faults before interturn short circuit and arc discharge faults. The work in this paper provides a new idea for the early interturn fault diagnosis of transformers. image
引用
收藏
页码:1871 / 1884
页数:14
相关论文
共 50 条
  • [1] Integrated Fuzzy Approach for Incipient Fault Detection in Power Transformers
    Patel, R. N.
    Thakur, H. S.
    [J]. 2016 IEEE INDUSTRIAL ELECTRONICS AND APPLICATIONS CONFERENCE (IEACON), 2016, : 211 - 218
  • [2] Interturn Fault Detection in Transformers Using Search Coil Based Method
    Sonwane, Lokesh Y.
    Sandeep, K. Kamal
    Wakchaure, Pramil
    [J]. 2018 INTERNATIONAL CONFERENCE ON RECENT INNOVATIONS IN ELECTRICAL, ELECTRONICS & COMMUNICATION ENGINEERING (ICRIEECE 2018), 2018, : 2817 - 2821
  • [3] A New Method for Fault Detection and Identification of Incipient Faults in Power Transformers
    Ozgonenel, O.
    Kilic, Erdal
    Khan, M. Abdesh
    Rahman, M. Azizur
    [J]. ELECTRIC POWER COMPONENTS AND SYSTEMS, 2008, 36 (11) : 1226 - 1244
  • [4] Incipient fault detection for electric power transformers using neural modeling and the local statistical approach to fault diagnosis
    Rigatos, Gerasimos
    Siano, Pierluigi
    Piccolo, Antonio
    [J]. 2012 IEEE SENSORS APPLICATIONS SYMPOSIUM (SAS 2012), 2012, : 32 - 37
  • [5] A Fuzzy System for Detection of Incipient Fault in Power Transformers Based on Gas-in-Oil Analysis
    de Aquino, Ronaldo R. B.
    Lira, Milde M. S.
    Filgueiras, Taciana
    Ferreira, Heldemarcio
    Nobrega Neto, Otoni
    Silva, Agnaldo M. S.
    Asfora, Viviane K.
    [J]. 2010 IEEE INTERNATIONAL CONFERENCE ON FUZZY SYSTEMS (FUZZ-IEEE 2010), 2010,
  • [6] Leakage Inductances Calculation for Power Transformers Interturn Fault Studies
    Oliveira, Luis M. R.
    Marques Cardoso, Antonio J.
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2015, 30 (03) : 1213 - 1220
  • [7] INCIPIENT FAULT-DETECTION FOR EHV TRANSFORMERS
    VITOLS, AP
    FERNANDES, RA
    [J]. IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1980, 99 (01): : 9 - 9
  • [8] Dynamic Incipient Fault Forecasting for Power Transformers Using an LSTM Model
    Wang, Lin
    Littler, Tim
    Liu, Xueqin
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2023, 30 (03) : 1353 - 1361
  • [9] Sensitive incipient inter-turn fault detection algorithm for power transformers
    Venikar, Prasad A.
    Ballal, Makarand S.
    Umre, Bhimrao S.
    Suryawanshi, Hiralal M.
    [J]. IET ELECTRIC POWER APPLICATIONS, 2016, 10 (09) : 858 - 868
  • [10] A Multinomial DGA Classifier for Incipient Fault Detection in Oil-Impregnated Power Transformers
    Odongo, George
    Musabe, Richard
    Hanyurwimfura, Damien
    [J]. ALGORITHMS, 2021, 14 (04)