Seamless switching control strategy of a DC microgrid from grid to off grid based on power compensation and droop coefficient attenuation

被引:0
|
作者
Chen Q. [1 ]
Wang W. [1 ]
Yue Y. [1 ]
Jiang H. [1 ]
Tang X. [1 ]
Fan B. [1 ]
Zeng X. [1 ]
机构
[1] School of Electrical and Information Engineering, Changsha University of Science and Technology, Changsha
来源
Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control | 2022年 / 50卷 / 16期
基金
中国国家自然科学基金;
关键词
bus voltage; DC microgrid; energy storage converter; impulse current; seamless switching;
D O I
10.19783/j.cnki.pspc.211351
中图分类号
学科分类号
摘要
A seamless switching control strategy is key to ensuring the stable and reliable operation of a DC microgrid. Such a control strategy for a DC microgrid from grid to off grid based on power compensation and droop coefficient attenuation is presented. This solves the problem of slow bus voltage recovery and poor power quality in traditional switching control methods. During island detection, the grid-connected converter works in the voltage control mode, and the energy storage converter (ESC) works in the droop control mode. Through modeling and analysis, it is proved that the DC bus voltage is controllable during island detection when droop control is used, and thus the selection method of the droop factor is obtained. After the islanding detection is completed, the ESC power compensation and droop coefficients are reduced by the fixed function to achieve a seamless switch of ESC droop control and voltage control. This prevents DC bus voltage fluctuations and ESC current impacts which may occur because of abrupt changes in ESC control mode. The selection method of the attenuation function is discussed. The simulation results show that the proposed seamless handover control strategy can effectively solve the problem of DC bus voltage being uncontrollable during islanding detection, and can suppress the current impact caused by ESC mode switching when islanding detection is completed. © 2022 Power System Protection and Control Press. All rights reserved.
引用
收藏
页码:14 / 22
页数:8
相关论文
共 26 条
  • [1] CHENG Z, DUAN J, CHOW M., To centralize or to distribute: that is the question: a comparison of advanced microgrid management systems, IEEE Industrial Electronics Magazine, 12, 1, pp. 6-24, (2018)
  • [2] SONG Chunning, FU Dong, LI Xin, Application of bi-directional full-bridge DC/DC converter in DC micro-grid, Electrical Measurement & Instrumentation, 57, 18, pp. 128-132, (2020)
  • [3] WANG Jianjian, SUN Yuanyuan, MA Zhao, Et al., Study on grounding method and grounding fault characteristics of islanded DC microgrid, Distribution & Utilization, 38, 1, pp. 3-10, (2021)
  • [4] HUANG Kun, LI Yanman, ZHANG Xiaoyan, Et al., Research on power control strategy of household-level electric power router based on hybrid energy storage droop control, Protection and Control of Modern Power Systems, 6, 2, pp. 178-190, (2021)
  • [5] WANG Zihao, MU Longhua, FANG Zhongkai, Fault control strategy of a low-voltage microgrid based on droop control, Power System Protection and Control, 48, 22, pp. 84-89, (2020)
  • [6] YANG Q, JIANG L, ZHAO H, Et al., Autonomous voltage regulation and current sharing in islanded multi-inverter DC microgrid, IEEE Transactions on Smart Grid, 9, 6, pp. 6429-6437, (2018)
  • [7] QIU Lin, XU Lie, ZHENG Zedong, Et al., Control method of microgrid seamless switching, Transactions of China Electrotechnical Society, 27, 2, pp. 171-176, (2014)
  • [8] ZHANG Yuhan, DU Guiping, LEI Yanxiong, Et al., Current status and prospects of control strategies for a DC micro grid hybrid energy storage system, Power System Protection and Control, 49, 3, pp. 177-183, (2021)
  • [9] YANG Jinsheng, TANG Fen, WU Xuezhi, Et al., Coordinated control of bidirectional DC/AC converters in DC microgrid, Power Electronics, 55, 5, pp. 113-116, (2021)
  • [10] LI Junhui, FENG Xichao, YAN Gangui, Et al., Survey on frequency regulation technology in high wind penetration power system, Power System Protection and Control, 46, 2, pp. 163-170, (2018)