Experimental study of fire exposed expanded polystyrene (EPS) insulation protected by selected coverings

被引:0
|
作者
Olso, Brynhild Garberg [1 ]
Hauko, Anne-Marit [1 ]
Risholt, Birgit [1 ]
机构
[1] SINTEF Community, POB 4760 Torgarden, N-7465 Trondheim, Norway
关键词
Fire testing; Fire protective covering; Combustible insulation; Fire safety; Expanded polystyrene; EPS; Fire protection engineering; PERFORMANCE; FACADES; ETICS;
D O I
10.1016/j.heliyon.2024.e26309
中图分类号
O [数理科学和化学]; P [天文学、地球科学]; Q [生物科学]; N [自然科学总论];
学科分类号
07 ; 0710 ; 09 ;
摘要
Insulation products made of expanded polystyrene (EPS) are commonly utilized in buildings. However, Norwegian building regulations restrict the use of such combustible insulation due to an increased risk of fire spread and generation of smoke and toxic gases. Installation of fire protection coverings has been adopted as a mitigation strategy to address these safety risks. Notably, the current regulations lack pre -approved solutions describing what is considered an adequate protection of combustible insulation. The present study investigated the fire protection properties of selected coverings used to protect EPS insulation in inner walls. Eight comparative fire tests were conducted using an indicative fire resistance test furnace. The test specimens consisted of EPS blocks mounted on a wooden frame and covered with one or two layers of selected board coverings. The specimens were positioned vertically within the test furnace, and each fire test lasted for 10 or 15 min. Test results revealed that only two configurations consisting of either two layers of 12.5 mm gypsum boards or a combination of 12 mm oriented strand board (OSB) and 12.5 mm gypsum board showed no evidence of damage to the EPS substrate after a 15min fire exposure. Consequently, the findings suggest that a total covering thickness of at least 24.5 mm, comprising two layers of boards, is necessary to prevent adverse effects on EPS insulation. Furthermore, fire tests conducted on coverings with introduced damages and defects showed that the affected area around the damages and defects were limited. For the standard EPS substrate, this area extended from 28 mm to 90 mm, while for the fire -retardant EPS substrate from 28 mm to 75 mm after a 10 -min fire exposure. These results suggest that minor physical failures in the covering have limited impact on the fire safety of the system.
引用
收藏
页数:22
相关论文
共 50 条
  • [1] Experimental study of expanded polystyrene (EPS) External Thermal Insulation Composite Systems (ETICS) masonery facade reaction-to-fire performance
    Zhou, Biao
    Yoshioka, Hideki
    Noguchi, Takafumi
    Ando, Tatsuo
    [J]. THERMAL SCIENCE AND ENGINEERING PROGRESS, 2018, 8 : 83 - 92
  • [2] Innovative fire and water insulation foam using recycled plastic bags and expanded polystyrene (EPS)
    Fard, Parastoo Moghaddam
    Alkhansari, Maryam Gharavi
    [J]. CONSTRUCTION AND BUILDING MATERIALS, 2021, 305
  • [3] Fire Performance of External Thermal Insulation Composite System (ETICS) Facades with Expanded Polystyrene (EPS) Insulation and Thin Rendering
    Milan Hajduković
    Nataša Knez
    Friderik Knez
    Jerneja Kolšek
    [J]. Fire Technology, 2017, 53 : 173 - 209
  • [4] Fire Performance of External Thermal Insulation Composite System (ETICS) Facades with Expanded Polystyrene (EPS) Insulation and Thin Rendering
    Hajdukovic, Milan
    Knez, Natasa
    Kolsek, Jerneja
    Knez, Friderik
    [J]. FIRE TECHNOLOGY, 2017, 53 (01) : 173 - 209
  • [5] Experimental research on employed expanded polystyrene (EPS) for lightened sulfate heave of subgrade by thermal insulation properties
    Peng, Shuquan
    Wang, Fan
    Li, Xibing
    Fan, Ling
    [J]. GEOTEXTILES AND GEOMEMBRANES, 2020, 48 (04) : 516 - 523
  • [6] Lightweight structural cement composites with expanded polystyrene (EPS) for enhanced thermal insulation
    Dixit, Anjaneya
    Pang, Sze Dai
    Kang, Sung-Hoon
    Moon, Juhyuk
    [J]. CEMENT & CONCRETE COMPOSITES, 2019, 102 : 185 - 197
  • [7] The Impact of Climatic Factors to the Structure of Unprotected Expanded Polystyrene External Insulation on Building (Eps)
    Mickevicius, Edgaras
    Kicaite, Asta
    Buska, Andrius
    [J]. ADVANCED CONSTRUCTION 2012, 2012, : 133 - +
  • [8] Performance of molded expanded polystyrene (EPS) thermal insulation in below-grade applications
    Whalen, J
    [J]. INSULATION MATERIALS: TESTING AND APPLICATIONS, 4TH VOLUME, 2002, 1426 : 366 - 378
  • [9] Recycled EPS (expanded polystyrene) from food's packaging as a thermal insulation of roofs
    Medeiros, DS
    Marinho, GS
    [J]. Energy-Efficient, Cost-Effective and Environmentally-Sustainable Systems and Processes, Vols 1-3, 2004, : 233 - 240
  • [10] SOLUTIONS FOR THE WORRYING SITUATION OF EXTERNAL THERMAL INSULATION OF BUILDINGS WITH EXPANDED POLYSTYRENE (EPS) IN ROMANIA
    Florea, Vitalie
    Pastia, Cristian
    Luca, Septimiu-George
    Paulet-Crainiceanu, Fideliu
    [J]. NANO, BIO AND GREEN - TECHNOLOGIES FOR A SUSTAINABLE FUTURE CONFERENCE PROCEEDINGS, SGEM 2016, VOL II, 2016, : 209 - 215