Modeling temporal dual variations for return air temperature prediction of mK-level temperature-controlled clean chamber

被引:0
|
作者
Yu, Hangcheng [1 ]
Dong, He [2 ]
Zeng, Zhibo [1 ]
Cao, Di [1 ]
Zhang, Wei [1 ]
Wang, Pan [1 ]
Li, Xiaoping [1 ]
机构
[1] Huazhong Univ Sci & Technol, State Key Lab Digital Mfg Equipment & Technol, Wuhan 430074, Peoples R China
[2] China Univ Geosci, Sch Mech & Elect Informat, Wuhan 430074, Peoples R China
来源
关键词
Indoor temperature prediction; Time series forecasting; Gated recurrent unit (GRU); Air conditioning; Cleanroom; Precision temperature control; INDOOR TEMPERATURE;
D O I
10.1016/j.jobe.2024.108917
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Clean chamber with mK-level temperature stability is required for precision manufacturing and optical equipment to achieve nanoscale manufacturing tolerances and measurement accuracy, however, the equipped precision air conditioning system cannot respond immediately to temperature fluctuation in the chamber due to large time delay. Predicting the future return air temperature gives the control module a prescient ability to act in advance, thus aiding in temperature regulation. To this end, this paper deals with the mK-level temperature prediction problem under a high -precision temperature control situation, and a novel prediction network model dubbed TDVNet is designed based on convolutional neural network (CNN) and gated recurrent unit (GRU), where Temporal Dual Variations of time series data, namely variationsbetween -phases and variations -across -periods, are modeled to achieve a higher accuracy of return air temperature prediction. Utilizing chamber temperature data collected on -site for model training and evaluation, the experimental results show that capturing data change patterns from dual perspectives has reduced the root mean square error (RMSE) and mean absolute percentage error (MAPE) of the TDVNet model by 21.4% and 24.3%, respectively, compared to the model only capturing the variations -between -phases. Under a signal sampling interval of 10 s and a temperature fluctuation of (66.9 +/- 25.8) mK@10min, the TDVNet model can accurately predict the return air temperature change in the next 5 min, and the proportion of prediction errors within 15 mK in the test set can reach over 90.1%.
引用
收藏
页数:18
相关论文
共 5 条
  • [1] A novel dual-chamber microcapsule inspired by lotus seedpod for temperature-controlled fragrance release and thermal-regulation of fabrics
    Huo, Zihao
    Liu, Jiayin
    Yan, Jin
    Wang, Shuo
    Yang, Wenxiu
    Shan, Juchuan
    Hu, Xuemin
    COLLOIDS AND SURFACES A-PHYSICOCHEMICAL AND ENGINEERING ASPECTS, 2025, 717
  • [3] Modeling for vehicle cabin temperature prediction based on graph spatial-temporal neural network in air conditioning system
    He, Xinglei
    Wang, Yichun
    Guo, Fen
    Zhang, Xiaohan
    Duan, Xiuhui
    Pei, Jinchen
    ENERGY AND BUILDINGS, 2022, 272
  • [4] Groundwater Heat Pump (GWHP) system modeling and Thermal Affected Zone (TAZ) prediction reliability: Influence of temporal variations in flow discharge and injection temperature
    Lo Russo, Stefano
    Gnavi, Loretta
    Roccia, Emanuele
    Taddia, Glenda
    Verda, Vittorio
    GEOTHERMICS, 2014, 51 : 103 - 112
  • [5] The application of a high-density street-level air temperature observation network (HiSAN): Spatial and temporal variations of thermal and wind condition in different climatic condition types
    Chen, Yu-Cheng
    Hou, Kai-Shan
    Liao, Yu-Jie
    Honjo, Tsuyoshi
    Cheng, Fang-Yi
    Lin, Tzu-Ping