Degradation Phase Division of AC Contactor Contact System Based on Vibration Signal

被引:0
|
作者
Liu S. [1 ]
Zhou Z. [1 ]
Liu Y. [1 ]
Cao Y. [1 ]
Jiang X. [1 ]
Li J. [1 ]
机构
[1] Key Laboratory of Special Electric Machines and High Voltage Apparatus in the Ministry of Education, Shenyang University of Technology, Shenyang
来源
关键词
AC contactor; degraded state; FCM clustering; SRCC; stage division; vibration signal;
D O I
10.13336/j.1003-6520.hve.20221773
中图分类号
学科分类号
摘要
The problems of high redundancy of vibration signal and low accuracy of classification in the degradation stage exist in AC contactor contact system degradation, therefore,a method based on Spearman's rank correlation coefficient (SRCC) and fuzzy C-means clustering (FCM) is proposed to divide the degradation phase of the contact system. Firstly, the vibration signals of the opening and closing stages of the contact system throughout the life cycle are obtained through the full life test of the AC contactor, and the time domain and frequency domain characteristics reflecting the degradation state of the contacts are extracted from the results.Secondly, SRCC and principal component analysis are used to select feature and reduce feature dimensionality, and to construct performance degradation indicators. Thirdly, unsupervised learning (UL) FCM is introduced as a theoretical basis for dividing the contact system into 2 to 5 degradation stages. Finally, silhouette coefficient (SC), Calinski Harabasz score(CHS) and Dacies Bouldin index (DBI) are selected to evaluate the clustering effect internally, and five supervised classifiers are used to verify the accuracy of this method. The results show that the internal evaluation is the best when the contact system is divided into three degradation stages, the average recognition accuracy of five classifiers for the three degradation stages can reach 95.54%, and the degradation stage division is the most reasonable. The proposed method can be adopted to effectively solve the problem of signal redundancy and low accuracy of phase division, which can accurately realize the division of degradation phase of AC contactor contact system. © 2023 Science Press. All rights reserved.
引用
收藏
页码:4971 / 4982
页数:11
相关论文
共 32 条
  • [1] SU Xiuping, TIAN Haibo, MU Siye, Structural design and optimization of electromagnetic system for intelligent AC contactor, Electric Machines and Control, 24, 5, pp. 43-50, (2020)
  • [2] KAWASE Y, TATSUOKA S, YAMAGUCHI T, Et al., 3-D finite element analysis of operating characteristics of AC electromagnetic contactors, IEEE Transactions on Magnetics, 30, 5, pp. 3244-3247, (1994)
  • [3] ZHENG Shumei, LI Kui, LIU Zhengjun, Et al., Research on distributional characteristic of electrical endurance of AC contactor based on arc erosion, Proceedings of the CSEE, 37, 22, pp. 6730-6739, (2017)
  • [4] NIU Chunping, CHEN Degui, LI Xingwen, Et al., Simulation of contact bounce of AC contactor and study of its influence factors, Transactions of China Electrotechnical Society, 22, 10, pp. 85-90, (2007)
  • [5] ZHENG Xin, XU Zhihong, An exploration on the best breaking areas of AC contactors, Transactions of China Electrotechnical Society, 31, 7, pp. 198-206, (2016)
  • [6] SUN Shuguang, WANG Ruixiong, DU Taihang, Et al., Expected electrical life prediction of AC contactor based on rough set and evidence theory, Transactions of China Electrotechnical Society, 35, 10, pp. 2158-2169, (2020)
  • [7] YOSHIDA K, SHIMOTSUMA S, SAWA K, Et al., Various characteristics of electromagnetic contactor when arc discharge are generated only make arc, 2016 IEEE 62nd Holm Conference on Electrical Contacts (Holm), pp. 215-221, (2016)
  • [8] WU Z R, WU G C, CHEN C, Et al., A novel breaking strategy for electrical endurance extension of electromagnetic alternating current contactors, IEEE Transactions on Components, Packaging and Manufacturing Technology, 6, 5, pp. 749-756, (2016)
  • [9] LIU Shuxin, SONG Jian, LIU Yang, Et al., Research on motion analysis and fault diagnosis of contact system of AC contactor, Transactions of China Electrotechnical Society, 36, pp. 477-486, (2021)
  • [10] LI Kui, LI Xiaobei, ZHENG Shumei, Et al., Residual electrical life prediction for AC contactor based on BP neural network, Transactions of China Electrotechnical Society, 32, 15, pp. 120-127, (2017)