Design and Implementation of Substation Switching Operation Platform Based on Cloud-edge Cooperation

被引:0
|
作者
Chen J. [1 ]
Huang Y. [2 ]
Lin J. [1 ]
Liu D. [2 ]
Chen Z. [1 ]
Di F. [2 ]
机构
[1] State Grid Fujian Electric Power Company, Fujian Province, Fuzhou
[2] Beijing Key Laboratory of Research and System Evaluation of Power Dispatching Automation Technology, China Electric Power Research Institute, Haidian District, Beijing
来源
关键词
anti-misoperation; cloud-edge cooperation; cloud-edge interaction; dispatching and control cloud; switching operation;
D O I
10.13335/j.1000-3673.pst.2021.2082
中图分类号
学科分类号
摘要
With the rapid development of smart grid technology, the integrated automation technology of substations has achieved significant improvement. However, the automatic operation functions of monitoring, operating and maintaining are not perfect. For example, the switching operation depends mostly on the traditional manual operation with one step after another, which is inefficient and far from meeting the development needs of the power system. Based on the dispatching and control cloud platform, the cloud-edge coordination cooperation technology is used to realize the integrated online management and control in the whole process of delivering the dispatching order, getting the operation ticket, rehearsing and operating, which improves the efficiency and accuracy of the substation switching operation. Firstly, the cloud and the edge sides are determined based on the business roles of the cloud center, the workstations of the anti-misoperation, and the mobile APPs during the substation switching operation. Then, based on the whole process of the switching operation, the mechanisms of cloud-edge interaction and cloud-edge cooperation are designed to form a switching anti-misoperation platform with the "full perception of the running status, full process of the anti-misoperation, full online of the operation and full cooperation of the business" operation. The reputation mechanism is introduced to improve the anti-misoperation accuracy of the edge nodes. Finally, through experiments, the performance evaluation, system scalability and anti-misoperation accuracy of the cloud-edge model are verified and analyzed. The results show that the anti-misoperation platform designed in this paper has a certain advantages in improving the switching operation efficiency and accuracy. © 2023 Power System Technology Press. All rights reserved.
引用
收藏
页码:833 / 841
页数:8
相关论文
共 20 条
  • [1] Hao DAI, CHEN Kun, SHAO Xinyuan, Research and application of real-time error prevention technology in substation switching operation[J], Electric Engineering, 10, pp. 84-86, (2019)
  • [2] LIN Jinghuai, MI Weimin, LI Zeke, Safety anti-misoperation technology of remote operation of smart grid dispatching and control systems[J], Automation of Electric Power Systems, 39, 1, pp. 60-64, (2015)
  • [3] YUAN Xiaojun, Anti-misoperation behavior and improvement of switching in substation operation and maintenance, Low Carbon World, 10, pp. 106-107, (2018)
  • [4] LI Shengquan, QIAN Wenshu, Research on the current situation and development trend of smart substation technology[J], Power System and Clean Energy, 33, 12, pp. 59-64, (2017)
  • [5] CAO nan, LI Gang, WANG Dongqing, Key technologies and construction methods of smart substation[J], Power System Protection and Control, 39, 5, pp. 63-68, (2011)
  • [6] ZHANG Dongying, YANG Junwei, HUANG Jianyang, General method for automatic generation of operation task[J], Automation of Electric Power Systems, 42, 24, pp. 169-174, (2018)
  • [7] (2011)
  • [8] (2017)
  • [9] LI Gongxin, HUANG Wenying, REN Xiaohui, Research on anti-misoperation check in integrated dispatching and control system[J], Power System Protection and Control, 43, 7, pp. 97-102, (2015)
  • [10] ABE T,, GOTO H, MIZUTORI T, An expert system for generating switching sequences at substations[C], Proceedings of the International Workshop on Artificial Intelligence for Industrial Applications, pp. 326-331, (1988)