The Relationship between Mechanical Ventilation, Indoor Air Quality Classes, and Energy Classes in a Romanian Context

被引:3
|
作者
Vasile, Vasilica [1 ]
Iordache, Vlad [2 ]
Radu, Valentin Mihai [2 ]
Dragomir, Claudiu-Sorin [1 ,3 ]
机构
[1] Urbanism & Sustainable Spatial Dev URBAN INCERC, Natl Inst Res & Dev Construct, 266 Pantelimon Rd, Bucharest 021652, Romania
[2] Tech Univ Civil Engn Bucharest, CAMBI Res Ctr, 66 Pache Protopopescu Blvd, Bucharest 021407, Romania
[3] Univ Agron Sci & Vet Med Bucharest, Fac Land Reclamat & Environm Engn, 59 Marasti Ave, Bucharest 012244, Romania
关键词
building ventilation; indoor air quality; energy consumption; pollutants; human health; HEALTH; IMPACT; PERFORMANCE; MODEL;
D O I
10.3390/atmos15040444
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
Nowadays, indoor air quality (IAQ) and the energy performance of buildings are two main scientific and technical challenges because they are in direct connection with human health and the depletion of energy resources. In this study, we analyzed the influence of an outdoor air flow introduced through a mechanical ventilation system, focusing on the two aforementioned topics. A standardized ventilation rate (25 m3/h/person) led to an increase in the indoor O3 concentration (from 5 mu g/m3 to 50 mu g/m3) and, simultaneously, to a decrease in the indoor CO2 concentration (from 2000 mg/m3 to 800 mg/m3), a decrease in the PM2.5 concentration (from 300 mu g/m3 to 150 mu g/m3), and the maintenance of a constant indoor HCHO concentration. In our study, a new, single indoor air quality index, IIAQ, is proposed. This new index presents different implications: on the one hand, it has the ability to simultaneously take into account several pollutant species, and on the other hand, it can prioritize the ventilation strategy that responds to the extreme values of a certain pollutant. Moreover, indoor air quality classes were elaborated, similar to energy classes. The possibility of using this new index simultaneously with energy consumption may lead to ventilation strategies that are adaptative to dynamic outdoor pollutant concentrations.
引用
收藏
页数:19
相关论文
共 50 条
  • [1] Associated relationship between ventilation rates and indoor air quality
    Cao, Shi-Jie
    Zhu, Dong-Hao
    Yang, Yin-Bao
    RSC ADVANCES, 2016, 6 (112): : 111427 - 111435
  • [2] Innovative Mechanical Ventilation Control for Enhanced Indoor Air Quality and Energy Efficiency
    Miracco, Giovanni
    Nicoletti, Francesco
    Ferraro, Vittorio
    Kaliakatsos, Dimitrios
    Energy Engineering: Journal of the Association of Energy Engineering, 2025, 122 (03):
  • [3] Ventilation for good indoor air quality and energy efficiency
    Awbi, Hazim B.
    SUSTAINABLE SOLUTIONS FOR ENERGY AND ENVIRONMENT, EENVIRO 2016, 2017, 112 : 277 - 286
  • [4] Energy efficient ventilation and indoor air quality in the context of COVID-19-A systematic review
    Moghadam, Talie T.
    Morales, Carlos E. Ochoa
    Zambrano, Maria J. Lopez
    Bruton, Ken
    O'Sullivan, Dominic T. J.
    RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2023, 182
  • [5] Relationships between ventilation and indoor air quality: A review
    Godish, T
    Spengler, JD
    INDOOR AIR, 1996, 6 (02) : 135 - 145
  • [6] A COMPARISON OF OPEN-AIR WITH INDOOR CLASSES
    McCall, W. A.
    Johnson, Abigail E.
    TEACHERS COLLEGE RECORD, 1918, 19 (04): : 35 - 51
  • [7] Ventilation and Indoor Air Quality
    Kumar, Ashok
    Moreno-Rangel, Alejandro
    Khan, M. Amirul, I
    Piasecki, Michal
    ATMOSPHERE, 2022, 13 (10)
  • [8] Energy efficiency and indoor air quality of seminar rooms in older buildings with and without mechanical ventilation
    Maas, Stefan
    Antunes, Joel Da Cruz
    Steffgen, Georges
    BAUPHYSIK, 2019, 41 (05) : 243 - 251
  • [9] Ventilation Strategies for Good Indoor Air Quality and Energy Efficiency
    Seppanen, Olli
    INTERNATIONAL JOURNAL OF VENTILATION, 2008, 6 (04) : 297 - 306
  • [10] RELATIONSHIP BETWEEN ENERGY-CONSERVATION IN BUILDINGS AND INDOOR AIR-QUALITY
    KIMURA, K
    JOURNAL OF THERMAL BIOLOGY, 1993, 18 (5-6) : 541 - 543