A novel meta-learning network for partial discharge source localization in gas-insulated switchgear via digital twin

被引:0
|
作者
Yan, Jing [1 ]
Wang, Yanxin [1 ]
Zhou, Yang [1 ]
Wang, Jianhua [1 ]
Geng, Yingsan [1 ]
机构
[1] Xi An Jiao Tong Univ, State Key Lab Elect Insulat & Power Equipment, Xian, Shaanxi, Peoples R China
关键词
artificial intelligence; fault location; gas insulated substations; partial discharges; ELECTROMAGNETIC-WAVE; LOCATION;
D O I
10.1049/gtd2.13156
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Due to the requirement for highly precise synchronous sampling and the substantial reliance on time difference calculations, the current partial discharge (PD) localization based on the time difference of arrival is only applicable in certain situations. As digital twin technology has advanced, it is possible to employ virtual models to support gas-insulated switchgear (GIS) PD localization. To do this, we propose a meta-learning (ML) network with the aid of digital twin for actual GIS PD localization. Firstly, a GIS digital twin model was established to acquire an auxiliary simulated sample library. Then, a temporal convolutional network is established to extract the discriminable features, effectively obtain the time dependence between features, and improve the accuracy of localization. Next, ML is adopted to quickly learn meta-knowledge that can be applied across tasks, and the model's sensitivity to task changes is improved. Finally, the model is fine-tuned through a limited number of samples from the target task, and high precise PD localization is achieved. The experimental results demonstrate that the ML has an average localization error of only 9.25 cm and a probability density rose to 93% within 20 cm, which is clearly superior to previous methods. This paper proposes a meta-learning network with the aid of digital twin for actual GIS PD localization. It does not require obtaining a large number of actual samples on GIS for training; instead, with the assistance of the digital twin model, practical GIS PD localization can be achieved. image
引用
收藏
页码:1785 / 1794
页数:10
相关论文
共 50 条
  • [1] Partial discharge diagnosis via a novel federated meta-learning in gas-insulated switchgear
    Yan, Jing
    Wang, Yanxin
    Liu, Wenchao
    Wang, Jianhua
    Geng, Yingsan
    [J]. REVIEW OF SCIENTIFIC INSTRUMENTS, 2023, 94 (02):
  • [2] Collaborative Domain Adaptation Network for Partial Discharge Source Localization in Gas-Insulated Switchgear
    Wang, Yanxin
    Yan, Jing
    Qi, Meirong
    Yang, Zhou
    Wang, Jianhua
    Geng, Yingsan
    [J]. IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 2023, 72
  • [3] Simultaneous Partial Discharge Diagnosis and Localization in Gas-Insulated Switchgear via a Dual-Task Learning Network
    Wang, Yanxin
    Yan, Jing
    Yang, Zhou
    Xu, Zhuofan
    Qi, Zhenkang
    Wang, Jianhua
    Geng, Yingsan
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2023, 38 (06) : 4358 - 4370
  • [4] Domain-alignment multitask learning network for partial discharge condition assessment with digital twin in gas-insulated switchgear
    Yan, Jing
    Wang, Yanxin
    Zhang, Wenjie
    Wang, Jianhua
    Geng, Yingsan
    Srinivasan, Dipti
    [J]. MEASUREMENT SCIENCE AND TECHNOLOGY, 2024, 35 (06)
  • [5] Novel metric-based meta-learning model for few-shot diagnosis of partial discharge in a gas-insulated switchgear
    Wang, Yanxin
    Yan, Jing
    Yang, Zhou
    Qi, Zhenkang
    Wang, Jianhua
    Geng, Yingsan
    [J]. ISA TRANSACTIONS, 2023, 134 : 268 - 277
  • [6] Mutitask Learning Network for Partial Discharge Condition Assessment in Gas-Insulated Switchgear
    Wang, Yanxin
    Yan, Jing
    Zhang, Wenjie
    Yang, Zhou
    Wang, Jianhua
    Geng, Yingsan
    Srinivasan, Dipti
    [J]. IEEE TRANSACTIONS ON INDUSTRIAL INFORMATICS, 2024,
  • [7] Research on Gas-Insulated Switchgear Partial Discharge Diagnosis and Location Method Based on Multi-Task Meta-Learning
    Wang, Yanxin
    Yan, Jing
    Geng, Yingsan
    Liu, Zhiyuan
    Wang, Jianhua
    [J]. Hsi-An Chiao Tung Ta Hsueh/Journal of Xi'an Jiaotong University, 2024, 58 (07): : 105 - 115
  • [8] A novel federated deep learning framework for diagnosis of partial discharge in gas-insulated switchgear
    Wang, Yanxin
    Yan, Jing
    Jing, Qianzhen
    Wang, Jianhua
    Geng, Yingsan
    [J]. MEASUREMENT SCIENCE AND TECHNOLOGY, 2022, 33 (09)
  • [9] Recurrent Neural Network for Partial Discharge Diagnosis in Gas-Insulated Switchgear
    Minh-Tuan Nguyen
    Viet-Hung Nguyen
    Yun, Suk-Jun
    Kim, Yong-Hwa
    [J]. ENERGIES, 2018, 11 (05)
  • [10] Multi-source partial discharge diagnosis in gas-insulated switchgear via zero-shot learning
    Wang, Yanxin
    Yan, Jing
    Wang, Zhanbei
    Zhao, Danchen
    He, Ruixin
    Wang, Jianhua
    Geng, Yingsan
    [J]. MEASUREMENT, 2023, 217