Calculation of Electric Field and Space Charge Distribution of HVDC Cable Test Terminal Under Different Voltages

被引:0
|
作者
Zhao P. [1 ]
Chen Z. [1 ,2 ]
Zhao J. [1 ]
Ouyang B. [1 ]
Zhu T. [2 ]
Wang S. [2 ]
机构
[1] State Key Laboratory of Power Grid Environmental Protection, China Electric Power Research Institute, Wuhan
[2] State Key Laboratory of Electrical Insulation and Power Equipment, Xi'an Jiaotong University, Xi'an
来源
关键词
DC cables; Electric field; Impulse voltage; Space charge; Water-oil terminal;
D O I
10.13336/j.1003-6520.hve.20200944
中图分类号
学科分类号
摘要
The test terminal is an important part of the electrical performance test of HVDC. Based on the water terminal of AC cable, this paper creates the model of water-oil terminal of DC cable. In order to study the electric field and charge density distribution of the HVDC water-oil terminal under impulse voltage, a simulation model of the electric field-space charge of the water-oil terminal is established. The injection of space charge and the interaction between space charge and electric field are fully considered in this model. Secondly, the correctness of the model is verified by comparing with the experimental data. Finally, the electric field and the charge density distribution under six kinds of impulse voltages recommended by GB/T 31489.1 are studied. Meanwhile, the electric field intensity and charge density at the water-oil interface are compared. It is found that the lightning impulse voltage will generate the largest electric field at the water-oil interface among the six operating voltages, which exceeds the breakdown field intensity of water. Therefore, the water-oil terminal is not recommended to participate in the lightning impulse test. The research provides a valuable reference for design and development of the HVDC test terminal. © 2021, High Voltage Engineering Editorial Department of CEPRI. All right reserved.
引用
收藏
页码:4087 / 4094
页数:7
相关论文
共 21 条
  • [1] CHEN Xin, LI Wenpeng, LI Zhenyu, Et al., Prospect on key technology of the XLPE insulation materials and HVDC cables, High Voltage Engineering, 46, 5, pp. 1571-1579, (2020)
  • [2] WU Guofang, Research on the influence of defects in HVDC cable accessories on the electric field distribution, (2017)
  • [3] ZHAO Jiankang, ZHAO Peng, CHEN Zhengzheng, Et al., Review on progress of HVDC cables insulation materials, High Voltage Engineering, 43, 11, pp. 3490-3503, (2017)
  • [4] LIU Xia, YU Qinxue, LIU Minghao, Et al., DC E-t characteristics of 160 kV DC XLPE cable insulation, High Voltage Engineering, 45, 1, pp. 136-141, (2019)
  • [5] XIONG Jun, ZHANG Qiang, MA Guoming, Et al., Commissioning test methods for large capacity and long-distance AC XLPE power cable, High Voltage Engineering, 44, 11, pp. 3727-3735, (2018)
  • [6] ZHANG Hongliang, ZHANG Jianmin, YU Hongmiao, Et al., Design and test verification of China's first ± 525 kV XLPE insulated DC cable, Southern Power System Technology, 12, 1, pp. 1-6, (2018)
  • [7] CAO Jingying, CHEN Jie, ZHOU Zhicheng, Et al., Optimization of multiple resonance systems withstand voltage test method for long distance power cable, High Voltage Engineering, 44, 5, pp. 1692-1698, (2018)
  • [8] WANG Jingyu, Development of 110 kV deionized water test terminal, Electric Wire & Cable, 5, pp. 45-46, (1986)
  • [9] YANG Liming, OUYANG Benhong, MENG Shaoxin, Water treatment apparatus for power cable test terminal, (2009)
  • [10] KONG Dewu, Test terminal of XLPE cable, Electric Wire & Cable, 6, pp. 32-37, (1993)