Statistical Analysis of Long-Term Measured Electric Field of the Operating ±800 kV HVDC Bipolar Transmission Lines

被引:1
|
作者
Xie, Huichun [1 ,2 ]
Zhang, Jiangong [2 ]
Yao, Weifang [3 ]
Zhang, Yemao [2 ]
Xu, Jilai [2 ]
Gan, Zheyuan [2 ]
机构
[1] China Elect Power Res Inst CEPRI, Beijing 100192, Peoples R China
[2] State Key Lab Power Grid Environm Protect PGEP, Wuhan 430074, Peoples R China
[3] State Grid Anhui Elect Power Res Inst, Hefei 230601, Peoples R China
关键词
Electric fields; Meteorology; Transmission line measurements; HVDC transmission; Electric variables measurement; Wind speed; Correlation; HVDC bipolar lines; electric field; long-term measurement; statistics; meteorological parameters; correlation coefficient; Random Forests; variable importance measure; RANDOM FORESTS; GROUND-LEVEL; ION CURRENTS; CORONA; HUMIDITY; VOLTAGE; AIR;
D O I
10.1109/TPWRD.2024.3349535
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Presently, there is a lack of understanding regarding the distribution of the DC electric field of actual operating bipolar +/- 800 kV lines and its statistical correlation with meteorological factors. A 13-month measurement has been conducted for the operating +/- 800 kV HVDC bipolar transmission lines in China, from which the statistical variation of the DC electric field at the ground level were obtained across various seasons. It is found that electric field distribution is asymmetric except for summer and the average values of electric field statistics for all seasons are similar to those in autumn. The correlation between the meteorological parameters and the electric field was analyzed with correlation coefficients and Random Forests algorithm. And it indicates the wind speed perpendicular to lines, relative humidity and air pressure is the most influential meteorological parameters.
引用
收藏
页码:1040 / 1050
页数:11
相关论文
共 38 条
  • [1] Analysis of ionized field under ±800kV HVDC transmission lines
    Lu, Tiebing
    Zhao, Jie
    Cui, Xiang
    Feng, Han
    [J]. 2006 17TH INTERNATIONAL ZURICH SYMPOSIUM ON ELECTROMAGNETIC COMPATIBILITY, VOLS 1 AND 2, 2006, : 416 - +
  • [2] Analysis of coupling characteristics of hybrid electric field in the 750kV HVAC and ± 800kV HVDC parallel transmission lines
    Sun, Qiang
    Wu, Jian
    Lv, Haiping
    Han, Wen
    Wang, Lv
    Min, Jianwen
    Zhang, Qian
    Li, Yinfei
    Li, Xuebao
    [J]. 2017 IEEE 5TH INTERNATIONAL SYMPOSIUM ON ELECTROMAGNETIC COMPATIBILITY (EMC-BEIJING), 2017,
  • [3] LONG-TERM STATISTICAL STUDY OF THE CORONA ELECTRIC-FIELD AND ION-CURRENT PERFORMANCE OF A +/-900-KV BIPOLAR HVDC TRANSMISSION-LINE CONFIGURATION
    MARUVADA, PS
    DALLAIRE, RD
    HEROUX, P
    RIVEST, N
    [J]. IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1984, 103 (01): : 76 - 83
  • [4] Statistical evaluation and numerical analysis of effect of transverse wind on ionized field of ±800 kV UHVDC operating transmission lines
    Yi, Yong
    Zhang, Chuyan
    Wang, Liming
    Chen, Zhengying
    [J]. ELECTRIC POWER SYSTEMS RESEARCH, 2016, 140 : 560 - 567
  • [5] Resultant Electric Field Reduction With Shielding Wires Under Bipolar HVDC Transmission Lines
    Tian, Feng
    Yu, Zhanqing
    Zeng, Rong
    Yin, Han
    Zhang, Bo
    Liu, Lei
    Li, Min
    Li, Ruihai
    He, Jinliang
    [J]. IEEE TRANSACTIONS ON MAGNETICS, 2014, 50 (02) : 221 - 224
  • [6] Electric Field Calculation of ±800kV Transmission Lines by Surface Charge Method
    Li Shizuo
    [J]. 2011 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2011,
  • [7] Computational analysis of total electric field under ± 800 kV UHVDC transmission lines with cuboid buildings nearby
    He, Kun
    Wang, Tahan
    Chen, Bo
    Cao, Fangyuan
    Xie, Li
    Ma, Xiaoqian
    Wang, Yifan
    Lu, Jiayu
    Ju, Yong
    Sun, Ming
    Zeng, Mingquan
    [J]. ELECTRICAL ENGINEERING, 2024,
  • [8] CORONA STUDIES FOR BIPOLAR HVDC TRANSMISSION AT VOLTAGES BETWEEN +/- 600-KV AND +/- 1200-KV .1. LONG-TERM BIPOLAR LINE STUDIES
    MARUVADA, PS
    TRINH, NG
    DALLAIRE, RD
    RIVEST, N
    [J]. IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1981, 100 (03): : 1453 - 1461
  • [9] LONG-TERM AUDIBLE NOISE AND RADIO NOISE PERFORMANCE OF AMERICAN ELECTRIC POWERS OPERATING 765 KV LINES
    KOLCIO, N
    DIPLACIDO, J
    HAAS, RJ
    NICHOLS, DK
    [J]. IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1979, 98 (06): : 1853 - 1859
  • [10] Conductor Surface Conditions Effects on the Ion-Flow Field of Long-Term Operating Conductors of the HVDC Transmission Line
    Yi, Yong
    Zhang, Chuyan
    Wang, Liming
    Chen, Zhengying
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2017, 32 (05) : 2171 - 2178