POWER-FACTOR IMPROVEMENT OF 3-PHASE UNBALANCED LOADS WITH NONSINUSOIDAL SUPPLY VOLTAGE

被引:0
|
作者
CZARNECKI, LS
机构
关键词
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Three-phase load asymmetry causes a useless current loading of the supply source and this loading increases even more if the supply voltage is non-sinusoidal. This loading can be expressed quantitatively with the unbalanced current i(u) of RMS value \\i(u)\\. A whole compensation of the unbalanced current iu was proved to be possible with reactive balancing circuits, however, it may be very complex. This paper shows that a substantial minimization of the unbalanced current i(u) may be achieved with such a circuit, but of much lower complexity. The method suggested requires that the unbalanced admittances A(n) of the load for harmonic frequencies are known. A harmonic analysis that provides the complex RMS values of the phase voltages and currents harmonics in a cross-section between the load and the source enables us to determine these admittances and design the balancing circuit. It was shown, moreover, that the reduction of the unbalanced current i(u) can be integrated with the reactive current i(r) minimization.
引用
收藏
页码:67 / 74
页数:8
相关论文
共 50 条