Distance protection of multiple-circuit shared tower transmission lines with different voltages and underground cable sections

被引:1
|
作者
da Silva, Filipe Faria [1 ]
Bak, Claus L. [1 ]
Bukh, Bjarne [2 ]
机构
[1] Aalborg Univ, Aalborg, Denmark
[2] Energinet, Fredericia, Denmark
来源
关键词
power transmission protection; earthing; relay protection; fault currents; power overhead lines; power transmission faults; underground cables; fault location; power cables; poles and towers; overhead line conductors; multiple-circuit shared tower transmission lines; underground cable sections; fault current magnitude; distance protection relays; short-circuit magnitude; short-circuit powers; voltage levels; fault analysis; earth continuity conductor; voltage line; line configurations; grounding impedance;
D O I
10.1049/joe.2018.0156
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
Multiple-circuit transmission lines combining different voltage levels in one tower present extra challenges when setting a protection philosophy, as faults between voltage levels are possible. This study analyses faults in multiple-circuit transmission lines that are partly underground cable, by investigating the impact of the cable section on the fault current magnitude and operation of distance protection relays, without pilot scheme. The study shows that a cable's bonding configuration and layout have a small impact on the short-circuit magnitude, whereas the screen's grounding impedance and the presence of an earth continuity conductor impact the fault current magnitude. It was also demonstrated that distance protection relays settings used to protect the higher voltage line against single-phase-to-ground faults are capable of protecting the line against combined faults, for typical line configurations and short-circuit powers.
引用
收藏
页码:961 / 966
页数:6
相关论文
共 48 条
  • [1] Deploying correct fault loop in distance protection of multiple-circuit shared tower transmission lines with different voltages
    Bak, Claus Leth
    da Silva, Filipe Faria
    [J]. JOURNAL OF ENGINEERING-JOE, 2018, (15): : 1087 - 1090
  • [2] Distance protection of multiple-circuit shared tower transmission lines with different voltages - Part II: fault loop impedance
    da Silva, Filipe Faria
    Bak, Claus L.
    [J]. IET GENERATION TRANSMISSION & DISTRIBUTION, 2017, 11 (10) : 2626 - 2632
  • [3] Distance protection of multiple-circuit shared tower transmission lines with different voltages - Part I: fault current magnitude
    da Silva, Filipe Faria
    Bak, Claus L.
    [J]. IET GENERATION TRANSMISSION & DISTRIBUTION, 2017, 11 (10) : 2618 - 2625
  • [4] Fault Locating for Inhomogeneous Multiple-Circuit Transmission Lines with Shared Towers
    Xu, Z. Y.
    Yan, X. Q.
    Ran, L.
    Zhang, X.
    [J]. 2012 IEEE POWER AND ENERGY SOCIETY GENERAL MEETING, 2012,
  • [5] Method to measure the unbalance of the multiple-circuit transmission lines on the same tower and its applications
    Wang, Yufei
    Xu, Xing
    Xue, Hua
    [J]. IET GENERATION TRANSMISSION & DISTRIBUTION, 2016, 10 (09) : 2050 - 2057
  • [6] Analysis of ground distance protection for quadruple-circuit transmission lines on the same tower
    Zhang, Ying
    Tai, Neng-Ling
    [J]. Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2010, 38 (12): : 1 - 6
  • [7] Research on a New Method to Measure Unbalance of Multiple-Circuit Transmission Lines on the Same Tower Considering the Impact of Ground Wire
    Wang, Yu Fei
    Xu, Xing
    Xue, Hua
    Sun, Lu
    [J]. 2015 IEEE International Conference on Applied Superconductivity and Electromagnetic Devices (ASEMD), 2015, : 431 - 432
  • [8] Investigation of Short Circuit between Transmission Lines with Different Voltages
    Barakat, Mohammed A.
    Hatata, Ahmed Y.
    Badran, Ebrahim A.
    [J]. 2017 NINETEENTH INTERNATIONAL MIDDLE-EAST POWER SYSTEMS CONFERENCE (MEPCON), 2017, : 1145 - 1150
  • [9] Study on A New Earth-fault Distance Protection for Four-circuit Transmission Lines on The Same Tower
    Guo Peiyu
    Yu Zhongan
    Tai Nengling
    Fan Chunju
    [J]. MECHATRONICS AND INTELLIGENT MATERIALS III, PTS 1-3, 2013, 706-708 : 1574 - +
  • [10] The study of ground distance protection of 500kV quadruple-circuit transmission lines On the same tower
    Sun, Shujie
    Tai, Nengling
    Bo, Zhinqian
    [J]. 2008 PROCEEDINGS OF THE 43RD INTERNATIONAL UNIVERSITIES POWER ENGINEERING CONFERENCE, VOLS 1-3, 2008, : 436 - +